1 Publication 1756-UM514B-EN-P - February 2003
Chapter
9
Using RSLogix 5000 in Remote I/O and Block
Transfer Applications
Using This Chapter
This chapter describes how to use RSLogix 5000 with your
1756-DHRIO module in remote I/O and block transfer applications.
For more information on RSLogix 5000, see the online help.
Using RSLogix 5000 in
1756-DHRIO Module
Remote I/O Applications
When you use the 1756-DHRIO module for remote I/O, you must
follow these basic steps:
1. Add the 1756-DHRIO module to the project.
2. Configure the 1756-DHRIO module, including setting the
appropriate channels for Remote I/O.
3. Add a remote I/O adapter to the project.
4. Configure the remote I/O adapter.
5. Download the project to the controller.
6. Begin application operation (i.e. go online).
7. If necessary, change the configuration for all modules and
adapters in the project.
For information about: See page
Using RSLogix 5000 in 1756-DHRIO Module
Remote I/O Applications
9-1
Using RSLogix 5000 in 1756-DHRIO Module
Block Transfer Applications
9-9
IMPORTANT
When using the 1756-DHRIO module in remote I/O
mode on channels A & B a remote I/O node cannot
be duplicated. Channel A’s nodes must all be unique
to B’s nodes.