11-8 Block Transfers with the 1756-DHRIO Module
Set the Module Switches
In this application, channel B on the 1756-DHRIO module must be set
for RIO. Channel A can be used for remote I/O or DH+, regardless of
the usage assigned to channel B. For more information on setting
switches on the 1756-DHRIO module, see
page 1-5.
Set the switches on the 1756-CNB modules to the correct network
addresses. The 1756-CNB module in system #1 uses network
address
01 and the 1756-CNB module in system #2 uses network
address 23. For more information on setting the switches on the
1756-CNB module, see
page 4-9.
Configure First 1756-CNB Module
Use RSLogix 5000 to configure the 1756-CNB module. Figure 11.7
shows some sample configuration screens for the first 1756-CNB
module in this example.
Figure 11.7
For more information on configuring a 1756-CNB module in a remote
I/O application, see
Chapter 9, or the RSLogix 5000 online help.
1
Also described on page 1-5
2