42 Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Chapter 2 Plan the Kinetix 6000 Drive System Installation
Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is
used in the Bulletin 2094 system and mounted above the IAM module:
The clean zone (C) is to the right and beneath the Bulletin 2094 system
(gray wireway).
The dirty zone (D) is to the left and above the Bulletin 2094 system, and
above and below the LIM module (black wireway).
The LIM VAC output is very dirty (VD). Use shielded cable with a
braid clamp attached at both ends of the cable to reduce the rating to
dirty (D).
The Sercos fiber-optic cables are immune to electrical noise, but due to
their delicate nature, route them in the clean zone.
Figure 15 - Noise Zones (LIM mounted above IAM module)
(1) For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001
.
(2) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway.
(3) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
VD
D
D
D
D
C
C
C
Line Interface Module
Kinetix 6000
System
Dirty Wireway Clean Wireway
Motor Power Cables
Very dirty LIM/IAM
(1)
connections must be
shielded with braid
clamp at both ends.
I/O
(2)
and Feedback Cables
No sensitive
(3)
equipment within
150 mm (6.0 in.).
Route 24V DC I/O
shielded cable.
Route encoder/analog/registration
shielded cables.
Fiber-optic Cable

Table of Contents

Other manuals for Allen-Bradley Kinetix 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Kinetix 6000 and is the answer not in the manual?

Allen-Bradley Kinetix 6000 Specifications

General IconGeneral
Control TypeDigital
FeedbackResolver, Encoder
Protection RatingIP20
Power Range0.4…22 kW
CommunicationEthernet/IP
Ambient Temperature0°C to 50°C
AxisSingle-axis, Multi-axis
SafetySafe Torque-Off
Control ModesVelocity, Torque, Position
Relative Humidity5% to 95% (non-condensing)
Vibration Resistance5.9 m/s² (0.6 g) from 10 Hz to 500 Hz
Shock Resistance15 g, 11 ms
Storage Temperature-40°C to 70°C