28 Rockwell Automation Publication 6000-UM002E-EN-P - April 2018
Chapter 2 Drive System Layout
Figure 18 - Dead Bolt Counterpart Mounted to Cabinet
4. Bolt the cabinet door closed so the pins on the dead bolt counterpart make 
contact with the dead bolt assembly. Doing so should leave two marks of 
torque sealant or grease on the assembly where the pins made contact (See 
Figure 13).
5. Slightly loosen the adjustment bolts on the counterpart and make the 
necessary movements on the counterpart to ensure that the pins align with 
the landing plates on the dead bolt assembly. As the amount of counterpart 
movement required is an estimate, it may take a couple attempts to 
properly align the assembly.
6. Clean the torque seal/grease from the key interlock once finished aligning 
the counterpart.
Once properly aligned, the key should turn freely when the cabinet door is fully 
bolted shut. If the key does not function when the door is tightly bolted closed, 
adjustments will have to be made to the depth of the counterpart. This can be 
done by adding shims on the landing plate where the counterpart is mounted.
Besides the mechanical interlock, PowerFlex 6000 drives also provide 
GuardmasterĀ® safety limit switch on each cabinet door that interlocks with input 
switching devices.
When any of the cabinet doors are open, the drive will turn off the IGBT output. 
At the same time, a trip signal will be sent to the circuit breaker to open the 
circuit.
Two pairs of passive dry contacts (open and close) are provided to the user.
Place grease on
dead bolt pins here