Chapter 4 Parameters and Function Codes
P487 PID Control Proportional Gain 0.000 32.767 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 On/Off Y Y
P488 PID Control Integral Time 0.000 32.767 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 On/Off Y Y
P489 PID Control Differential Gain 0.000 32.767 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 On/Off Y Y
P490 PID Control Differential Time 0.000 32.767 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 On/Off Y Y
P491 PID Control Feedback Lower Limit 0.000 32.767 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Offline Y Y
P492 PID Control Feedback Upper Limit 0.000 32.767 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 Offline Y Y
P494User Analog Set-point Switch0 3000000000000 On/OffYY
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
ATTENTION: If you enter a value that is greater than the allowed range for the
parameter, the input field will turn red.