124 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
SSI Word Delay Time
To enter Delay values from +32,768…+65,535 µs, use this conversion
formula:
Desired Delay Value (in µs) - 65536 = Entered Delay Value (in µs).
As an example, for a 40 ms delay time, 40000 - 65536 = -25536
Sensor Resolution
To enter Resolution values from +32,768…+65,535 µs, use this conversion
formula:
Desired Resolution Value - 65536 = Entered Resolution Value.
As an example, for a 40,000 count sensor, 40000 - 65536 = -25536
Sensor Cycle
To enter Cycle values from +32,768…+65,535, use this conversion formula:
Desired Cycle Value - 65536 = Entered Cycle Value.
As an example, for 50,000 sensor cycle rotations, 50000 - 65536 =
-15536
Compare 0,1 Value
To enter Compare values from +2,147,483,647…+4,294,967,295, use this
conversion formula:
Desired Compare Value - 4,294,967,296 = Entered Compare Value.
As an example, for a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296

Table of Contents

Other manuals for Allen-Bradley Rockwell Automation 1734-AENT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Rockwell Automation 1734-AENT and is the answer not in the manual?

Allen-Bradley Rockwell Automation 1734-AENT Specifications

General IconGeneral
Model1734-AENT
CategoryNetwork Hardware
TypeEtherNet/IP Adapter
Ethernet Ports2
IP AddressingStatic or DHCP
Network AddressConfigurable via software
MountingDIN rail
Number of Ports2
Port TypeRJ45
Communication ProtocolEtherNet/IP
ManufacturerRockwell Automation
Power Supply24V DC
EnclosureOpen-style

Related product manuals