25 Publication 1734-UM011D-EN-P - May 2011
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 Software
What This Chapter Contains
In this example, a ControlLogix controller communicates with POINT I/O
modules via the 1734-AENT adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by
the data. The modules presented in this chapter use RSLogix 5000 software,
version 11.
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix5555 processor in
slot 1 and a 1756-ENBT bridge module in slot 3.
Topic Page
Set Up the Hardware 25
Create the Example Application 26
Configure the I/O 27
Add the Local EtherNet/IP Bridge to the I/O
Configuration
28
Add the POINT I/O Adapter to the I/O Configuration 30
Add the POINT I/O Modules to the I/O Configuration 33
Add the Relay Output Module 33
Add the Digital Output Module 36
Edit the Controller Tags 38
Create the Ladder Program 39
Download the Program to the Controller 39
Verify the Module Chassis Size 41
Configure the Adapter with Fixed IP Address 38
Recover From an Overloaded Adapter 44
You must use series C POINT I/O modules with the 1734-AENT
adapter. Series A or B POINT I/O modules will not work with
this adapter.