EasyManua.ls Logo

Allen-Bradley Rockwell Automation 1734-AENT - Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software; What This Chapter Contains

Allen-Bradley Rockwell Automation 1734-AENT
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45 Publication 1734-UM011D-EN-P - May 2011
Chapter
5
Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software
What This Chapter Contains
This chapter guides you through the steps required to configure your
POINT I/O Ethernet adapter for both direct connection and rack
optimization using RSLogix 5000 software.
You can mix communication formats for different I/O modules
communicating through the same adapter. I/O modules set up to use rack
optimization communicate at the rate of the RPI configured for the
1734-AENT adapter.
I/O modules configured for direct communication communicate at their own
set RPI and ignore the 1734-AENT adapter RPI. The modules presented in
this chapter have a configuration using RSLogix 5000 software, version 15.
The chapter contains the following main sections:
Topic Page
Set Up the Hardware 46
Create the Example Application 47
Configure the I/O Modules 48
Add the Local EtherNet/IP Bridge to the I/O
Configuration
48
Add the POINT I/O Adapter to the I/O Configuration 50
Add the POINT I/O Module and Configure for Direction
Connection
53
Add the POINT I/O Module and Configure For Rack
Optimization
55
Download the Program to the Controller 58
Verify the Module Chassis Size 59
Access Module Data 62
ATTENTION
You must use series C POINT I/O modules with the 1734-AENT
adapter. Series A or B POINT I/O modules will not work with
this adapter.

Table of Contents

Other manuals for Allen-Bradley Rockwell Automation 1734-AENT

Related product manuals