- INSTALLER HIGHTEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL-
9
3.1 - Installing the HRC
70
3 - INSTALLATION
3.1.1 - Installation site
The Heat Pump must always be transported in a vertical position,
even during installation. It can be manually transported using
2 26mm Ø bars in the holes provided. Do not use the hydraulic
connections to move the appliance, take hold of it using the four
bottom corners.
The installation must be carried out by a quali ed installer, taking
all necessary precautions to avoid any risk of accident or any
material damage.
The Heat Pump is speci cally designed to be installed outdoors,
in an open space which is not subject to excessive dust. Under no
circumstances must it be installed in enclosed premises.
It is designed to operate in rain, but it can also be installed under
a shelter as long as it is well ventilated (the opening should be
large enough to ensure that air can  ow freely to the air intake
point and the air rejection point on the fan).
ON THE GROUND OR
ON A PATIO
(open space)
NEXT TO A WALL
+ 3dB (A)
IN A CORNER
+ 6dB (A)
IN A YARD
+ 9dB (A)
TO THE SIDE OF A WINDOWUNDER A WINDOW
THE NOISE SCREEN MUST BE MADE FROM
INSULATED MATERIALS
CORRECT
CORRECT

Table of Contents