6 Parameter Settings and Functions
102 © Copyright Reserved Autonics Co., Ltd.
Digital input terminal function operates irrespective of 6.7.7 Lock , 6.7.9 Password settings
[
PAR5 → PWD], 8.3.1 Parameter mask.
6.7.4.2 Digital input key
With digital input key enabled in RUN mode, press and hold keys at the same time for 3
sec. to activate the preset function.
6.7.4.2.1. Digital input key settings [PAR5 → DI-K]
In order to use the digital input key feature, each function has to be first assigned to the keys.
Setting Description
STOP
RUN/STOP
AlRE
Forced alarm output deactivation
AT
Auto-tuning RUN/OFF(in case of control method is PID control)
OFF
Not using digital input key
Parameter Setting range
Unit
PAR5
DI-K
STOP / AlRE
STOP -
If the digital input key and the digital input terminal set equally, the digital input key does not act.
6.7.4.2.2. Digital input key use
Press the digital input keys on the front panel to execute the function assigned to the keys.
When in RUN mode, press and hold + keys for 3 sec. to execute the assigned function
(run/stop or alarm output deactivation).
If the same function is assigned to a digital input key and the digital input terminal, activation
takes place as an "or" function and deactivation as an "and" function. (However, this does not
apply to the Multi SV feature of digital input terminals.)
Digital input key functions operate irrespective of 6.7.9 Password settings [PAR5 → PWD], 8.3.1
Parameter mask.