7 Setting group parameter description
116 © Copyright Reserved Autonics Co., Ltd.
7.8 Password entry parameter
Parameter Description Set range Unit
Factory
default
PASS
Password Password entry.
0001 to 9999
(0001: read-only)
-
0001
7.9 Parameter change reset parameters
Changed
parameter
Description Reset parameter
IN-T
Input types
SV-N, AL!L, AL!H, AL@L, AL@H, AL#L, AL#H, SV0to
SV3, DB, hHYS, hOST, cHYS, cOST, RAMU, RAMD,
rUNT, L-RG, H-RG, DOT, L-SC, H-SC, dUNT, IN-B,
L-SV, H-SV, LBaT, LBaB, AoM1, FsL1, FsH1, AoM2,
FsL2, FsH2
UNIT
Temperature input unit
With the exception of L-RG, H-RG, DOT, L-SC, H-SC,
and dUNT, Input type does not affect input units.
H-SV
SV high-limit value When SV>H-SV, SV resets to H-SV.
L-SV SV low-limit value When SV<L-SV, SV resets to L-SV.
O-FT
Control output operation
mode
L-MV, H-MV, C-MD, ErMV, PrMV, StMV
C-MD
Temperature control
type
L-MV, H-MV, ErMV, PrMV, StMV
AL-1, AL-2,
AL-3
Alarm mode/option AL!L, AL!H, AL@L, AL@H, AL#L, AL#H