6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 83
Alarm output hysteresis applies to heater burnout alarm [HBA] in the same manner.
This parameter does not appear if Loop Break Alarm [LBA] or Sensor Break Alarm [SBA] is
selected.
6.4.5 Alarm N.O./N.C. [PAR4 A!N/A@N/A#N]
You can set the relay contact method in the event of an alarm output.
Setting Description
NO
Normally open
Stays open when normal and closes in the event of an alarm.
NC
Normally closed
Stays closed when normal and opens in the event of an alarm.
Parameter
Description
A!N Select contact type for alarm output 1.
A@N
Select contact type for alarm output 2.
A#N Select contact type for alarm output 3.
Setting
group
Parameter Setting range
Factory
default
Unit
PAR4
A!N
NO / NC NO - A@M
A#M
Front LED Indicators
Change
Alarm trigger
Alarm output
Front LED
NO
(normally open)
OFF Open
□ OFF
ON Close ■ ON
NC
(normally closed)
OFF Close
□ OFF
ON Open ■ ON

Table of Contents

Other manuals for Autonics TK Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TK Series and is the answer not in the manual?

Autonics TK Series Specifications

General IconGeneral
BrandAutonics
ModelTK Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals