7 Setting group parameter description
108 © Copyright Reserved Autonics Co., Ltd.
7.3 Parameter 1 setting group [ PAR1 ]
Parameter Description Set range Unit
Factory
default
R-S
RUN_STOP
Control Output
RUN/STOP
RUN / STOP
-
RUN
SV-N Multi SV No.
Multi SV number
selection
SV-0 / SV-1 / SV-
2 / SV-3
-
SV-0
CT-A
Heater current
monitoring
Heater current
monitoring
)0 to 5)0 (display
range)
A
-
AL!L Alarm1_low
Alarm output 1's
low-limit value
Offset Alarm: -F. S.
to F.S .
Absolute Value
Alarm: Within
display range.
//-
1550
AL!H
Alarm1_high
Alarm output 1's
high-limit value
AL@L
Alarm2_low
Alarm output 2's
low-limit value
AL@H Alarm2_high
Alarm output 2's
high-limit value.
AL@L
Alarm3_low
Alarm output 3's
low-limit value
AL@H Alarm3_high
Alarm output 3's
high-limit value.
SV-0
SV-0 set value SV-0 set value
Between L-SV and
H-SV
//-
0000
SV-1 SV-1 set value SV-1 set value
Between L-SV and
H-SV
//-
0000
SV-2
SV-2 set value SV-2 set value
Between L-SV and
H-SV
//-
0000
SV-3
SV-3 set value SV-3 set value
Between L-SV and
H-SV
//-
0000