7 Setting group parameter description
© Copyright Reserved Autonics Co., Ltd. 111
7.5 Parameter 3 setting group [ PAR3 ]
Parameter Description Set range Unit
IN-T
Input type Input type
See Input types
chart.
-
TCaH
UNIT Unit
Sensor
temperature unit
?C / ?F -
?C
L-RG Low input range
Analog low-limit
input value
Minimum range.
to H-RG - F. S .10%
Digit
0)00
H-RG
High input range
Analog high-limit
input value
L-RG+F. S .10% to
Maximum range.
Digit
1)00
DOT
Scaling decimal
point
Decimal point
position - scale
value
0 / )0 / )00 / )000 -
)0
L-SC Low scaling
Scale low-limit
display value
`999 to 9999 -
00)0
H-SC
High scaling
Scale high-limit
display value
`999 to 9999
-
10)0
dUNT
Display unit
indicator
Front unit display ?C / ?F / ?/O / OFF -
?/O
IN-B Input correction Input correction
-999 to 0999
(`9(9 to 99(9)
Digit
0000
MAvF Input digital filter
Moving average
digital filter
00)1 to12)0 Sec
00)1
L-SV
SV low-limit SV low-limit value
Input Low-limit [L-
SC] to H-SV-1digit
℃/℉/%
-200
H-SV
SV high-limit SV high-limit value
L-SV+1digit to
input high-limit [H-
SC]
℃/℉/%
1350
O-FT
Control operating
type
Control output
operation mode
Standard
HEAT /
COOL
-
HEAT
Heating &
Cooling
type
HEAT /
COOL /
H-C
H-C
C-MD
Control method
Temperature
control type
Standard
PID /
ONOF
-
PID
Heating &
Cooling
type
pP /
pON /
OnP /
OnON
pP
AtT
Auto-tuning type Auto-tuning mode TUN1 / TUN2
-
TUN1
OUT1
Output1
(SSR_Curr) type
OUT1 control
output type
SSR / CURR
-
CURR
O!SR
OUT1 SSR
function
OUT1 SSR drive
output type
STND / CYCL/
PHAS
-
STND
O!MA
OUT1 current
range
OUT1 current
output range
4-20 / 0-20
-
4-20
OUT2
Output2
(SSR_Curr) type
OUT2 control
output type
SSR / CURR
-
CURR
O@MA
OUT2 current
range
OUT2 current
output range
4-20 / 0-20 -
4-20