6 Parameter Settings and Functions
86 © Copyright Reserved Autonics Co., Ltd.
6.4.7.1 LBA monitoring time [PAR4 LBaT]
You can set the LBA monitoring time to check changes in the control subject's temperature.
Automatically setting with auto-tunning.
Regardless of alarm operation [AL-] (including LBA monitoring time as 0”), after running
auto-tuning, the integration time×2 value is saved automatically.
(If SV is out of the range of auto setting, it is set as max. or min. value of auto setting.)
Except input type changing, re-running auto-tuning, manual setting of LBA monitoring time,
it maintains the present SV.
Auto setting range: 0020 to 9999
Setting
group
Parameter Setting range
Factory
default
Unit
PAR4 LBaT 0000 to 9999 0000 Sec
6.4.7.2 LBA detection band [PAR4 LBaB]
You can set the minimum value of deviation change to decrease during LBA monitoring time.
Automatically setting with auto-tunning.
Except input type changing, re-running auto-tuning, manual setting of LBA monitoring time,
it maintains the present SV.
Regardless of alarm operation [AL-] (including LBA monitoring time as 0”), after running
auto-tuning, the integration time×2 value is saved automatically.
(If SV is out of the range of auto setting, it is set as max. or min. value of auto setting.)
Auto setting range
Temperature L: 00@0 to 10)0(unit: /)
Temperature H: 0002 to 01)0(unit: /)
Analog: 00)2 to 01)0(unit: %F.S.)
Setting
group
Parameter Setting range
Factory
default
Unit
PAR4 LBaB
Temperature H 000 to 999 002
/
Temperature L 00)0 to 99(9
00@0
/
Analog 0)00 to 10)0
00)2 %F.S .