Appendix B - Fault messages Power Board BSF_400
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 87
Fault category: Power
Fault message
Cause
Remedy
battery is not connected
position if no battery is to
be used
The relay fault warning
may occure if there is a
hardware fault.
Replace BSF-400 board.
BSF-400 Battery voltage to low
This message may occur
under start-up when
battery voltage is to low,
i.e. charging current is
>1100mA.
Message will clear when
charge current drops
below 400mA.
Fault category: Por Fau message Cause Remedy