BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 13 Autronica Fire and Security AS
If everything is in a normal condition the following text will appear in the
display:
RESET OK
NORMAL CONDITION
This text remains in the display for 15 seconds, and then the menu selection
will appear.
After resetting, one or more addresses may still be in an alarm condition.
This can be due to mecanical damage, water damage, the presence of smoke
still within the chamber or an electrical fault. The addresses still in the alarm
condition, will automatically be disabled (isolated from the rest of the
system).
The following text will appear in the display:
01 ALARM ADDRESS(ES) DISABLED
CONTROL PANEL IN ABNORMAL CONDITION
Contact technical personnel.
F: Close the door.
In normal condition only the “MAINS” indication lamp shall remain
illuminated when the door is closed.
While an address is automatically disabled, the amber (yellow) “DEVICES
STILL IN ALARM COND.” indication lamp also will be lit.
If the alarm condition disappears, the indicator lamp will turn off and the
address automatically restored to the system.