BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 35 Autronica Fire and Security AS
10.1 Sensitivity
The "SENSITIVITY" function enables the user to read the analogue value of
an individual detector(address), from a loop or from all addresses connected
to the control panel. The analogue value is automatically updated every 5th
second. To achieve all advantages available in this function, the optional
printer must be fitted to the control panel.
An analogue value may be seen even when the device is disabled.
If the "SENSITIVITY" function is selected by moving the cursor with the
arrow- and enter-keys, the following text will appear in the display:
SENSITIVITY
ADDRESS BEYOND-LIMIT POLLUTED RET MM
10.1.1 Address
By selecting "ADDRESS" the following text will appear in the display:
ADDRESS SENSITIVITY
SINGLE ADDRESS LOOP TOTAL RET MM
If "SINGLE-ADDRESS" is selected, the following text will appear in the
display:
ADDRESS SENSITIVITY
ADDRESS: 0000 RET MM
Here it is necessary to select the address number by moving the cursor to the
correct column and then set the number in question by using the ß or Ý
keys. When the correct address no. is set, operate the
↵
↵↵
↵ key.
If detector address 0001 is selected, the following text will appear in the
display:
ADDRESS: 0001
SENSITIVITY: 074 WHEN COMPLETED PRESS ↵
↵↵
↵
The analogue value (sensitivity) is updated every 5th second. The value will
alter slightly at each update due to minor environmental changes.
(During the first few seconds of the sequence the display will show
sensitivity = 000).
Sensitivity