BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 32 Autronica Fire and Security AS
9.3 Fault
If the "FAULT" function is selected the following text will appear in the
display:
TEST EARTH-FAULT ACTIVE
. . . . .
The test process takes one minute. It is indicated by dots appearing in the
display for the first half minute. Then the sequence is reversed the next half
minute. This test process is a real one, and an genuine earth fault is
introduced. The internal buzzer is activated. The test is terminated by
pressing the
button.
Normal test function gives earth fault on the central panel.
When this earth fault test sequence is finished, the next sequence will
automatically start. The following text will appear in the display:
TEST ADDRESS FAULT ACTIVE
. . . .
In this sequence the control panels ability to receive fault messages from the
detectors/detector-loops is tested. This sequence also lasts for one minute.
A fault message on address 0001 will be shown provided this address is not
disabled. The fault will activate the internal buzzer.
When this address test sequence is finished, the next sequence will
automatically start. The following text will appear in the display:
TEST BATTERY ACTIVE
. . . .
This sequence (which is a real battery capacity test) lasts for 10 seconds and
normally should not give any fault message. (This test is automatically
carried out by the BS-100 every day at 10:00 AM).
Before continuing operate the "SOUNDER SILENCE" and "RESET"
pushbuttons.