3.2 Actions to be taken in the event of a “FIRE” alarm:
A: Follow all precautions described in the local fire instructions step
by step.
When the scene of the fire is investigated and the necessary actions
are carried out, the sounders may be switchedoff.
B: Open the control front door.
C: Press the”SOUNDER SILENCE” button.
All alarm devices (including the internal buzzer) will be muted.
The red “FIRE” indication lamp will switch to steady light.
All alarm outputs from the control panel will be turned of when the
“SOUNDER SILENCE” button is pressed.
However, the message to the Fire Fighters (BMA-) remains on.
If the silent alarm function (day/night) is in operation, the time delay (T1)
will start. Alarm outputs and the BMA-output will not be ativated.
If the alarm is acknowledged within the delay period (T1) by operating the
“SOUNDER SILENCE”-button, an additional delay period (T2) will be
activated.
If the “SOUNDER SILENCE”-button not is operated within the delay
period T1 or reset within the delay period T2, the alarm outputs and BMA
will be activated.
The alarm delay of sounder outputs and the BMA-output applies only for
alarm from detectors. Alarms from manual call points or 2 or more
detectors, over-ride the alarm delays T1 + T2, and the sounder outputs and
the BMA-output will operate immediately.
Silent alarm/alarm organisations (list L3.11) is controlled by external
manual switch with time controlled relay or automatic from external clock.
If the “MORE ALARMS” indication lamp lights, please see section 4.1
D: Press “RESET”-button.
The following text will appear in the text display:
RESET PROCEDURE IN PROGRESS
WAIT..........................
Actions
!