BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 24 Autronica Fire and Security AS
7.1.3.2 Disable controls (BSJ-100/101)
When disabling the controls, the control-outputs from external control-
output modules BSJ-100/BSJ-101 will not operate at alarm.
If “OUT/IN-CONTROL”, “DISABLE”, “CONTROLS” are selected and
then the “CONTROLS”, the following text will appear in the display:
DISABLEMENT OF CONTROLS
DURATION 02 HOURS RET MM
Select duration time for disablement by means of the arrow key and press ↵
↵↵
↵.
The following text will appear in the display:
DISABLEMENT OF CONTROLS
DISABLEMENT EXECUTED
Press
↵
↵↵
↵, and the system will return to “DISABLE CONTROLS”, with
possibility to return to the main menu.
Output controls can be disabled/restored from a superior computer
through the communication line..
7.1.4 Disable sounders (AK) (can be password protected in different
countries
- see Appendix A).
When disabling sounder output(s), the sounder(s) will not be activated at
alarm. This is applicable for the 4 standard sounder outputs and the outputs
from external sounder output board (BSB-100).
If “OUT/IN-CONTROL”, “DISABLE” and then “SOUDERS” are selected,
the following text will appear in the display:
DISABLEMENT OF SOUNDERS
DURATION 02 HOURS RET MM
Select the duration time for disablement by means of the arrow key and
press ↵
↵↵
↵.
The following text will appear in the display:
DISABLE SOUNDERS
DISABLEMENT EXECUTED
Press ↵
↵↵
↵, an the system will return to the “DISABLE”-menu with possibility
to return to the main menu.