BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 46 Autronica Fire and Security AS
A.2.2 - LPC (England)
Disablement of loop (under service-menu) activates the internal buzzer.
If one or more addresses are still in alarm condition after the "RESET"
procedure, an operator acknowledge is required to have these addresses
disabled by pressing the ↵
↵↵
↵ key on the front panel (as SOLAS).
Disablement of internal buzzer is not allowed.
Disabling the sounders through the menu will illuminate the "SOUNDERS
DISABLED" lamp.
Disablement of the fire brigade output will illuminate the "FIRE BRIG.
DISABLED" lamp.
A.2.3 - Denmark
If one or more addresses are still in alarm condition after the "RESET"
procedure, an operators acknowledge is required to have these addresses
disabled by pressing the ↵
↵↵
↵ key on the front panel (as SOLAS).
BMA, BMFO, BMF and output controls are disabled when the front door is
open.
System fault is given after 30 minutes interrupt of 220V AC.
A.2.4 - Sweden
Inverted BMF-output (active when there is voltage on the control panel).
Internal buzzer is disabled when front door is open.
Sounder silence and reset button must be pressed for more than 2 seconds to
activate the function.
Custom specified address text is presented on line 2.