5-108
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Password
The setting (changing) of the key lock, communication lock, and loader lock can be
set disabled using the password.
Item (Bank) Display Contents Initial value User level
Password display
(Lock bank)
0 to 15
5: Password 1A to 2B display
0
(The initial value
becomes “0” when the
power is turned ON.)
Basic,
Standard,
High function
Password 1A
(Lock bank)
0000 to FFFF (Hexadecimal value) 0000 Basic,
Standard,
High function
Password 2A
(Lock bank)
0000 to FFFF (Hexadecimal value) 0000
Password 1B
(Lock bank)
0000 to FFFF (Hexadecimal value) 0000
Password 2B
(Lock bank)
0000 to FFFF (Hexadecimal value) 0000
When using only the key lock setting, the display can be made, but the setting
(changing) cannot be made.
When locked with the password, the display and setting cannot be made.
The display and setting of [Password 1A:
PS1A
] and [Password 2A:
PS2A
] can
be made only when [Password display:
PASS
] is “5” and the passwords of two
groups (1A and 1B, 2A and 2B) are matched.
The display and setting of [Password1B:
PS1b
] and [Password 2B:
PS2b
] can be
made only when [Password display:
PASS
] is “5”.
The value set in [Password1A:
PS
1A
] is automatically set to [Password1B:
PS
1b
].
The value set in [Password2A:
PS2A
] is automatically set to [Password2B:
PS2b
].
Handling Precautions
Before setting the passwords 1A to 2B, determine two hexadecimal values
to be used as passwords and make a note of them for future reference.
[
PASS
] is used to prevent incorrect password setting by limiting the
display conditions of passwords 1A to 2B.
When other values are set for passwords 1B and 2B after the values to be
used as passwords have been set for passwords 1A and 2A, the passwords
1A and 2A cannot be displayed and the key lock, communication lock
and loader lock cannot be changed.
This status is called “password lock status.
The settings, which cannot be changed by the key lock, cannot be
displayed in the password lock mode.
If the password lock cannot be unlocked, contact the azbil Group or its
dealer. At Azbil Corporation's factory, the password lock can be unlocked
by returning the setting to the initial setting. In this case, note that the
data, which has been set by the customer, cannot be saved (retained).