13-4
Chapter 13. SPECIFICATIONS
Control output
Relay output
Contact rating: NO side 250 V AC/30 V DC, 3 A (resistance load)
NC side 250 V AC/30 V DC, 1 A (resistance load)
Life:
50,000 cycles or more on NO side
100,000 cycles or more on NC side
Min. open/close
specifications:
5 V, 100 mA
Min. open time/
close times
250 ms
Motor relay output (model R1)
Contact type: 1c (2 circuits: A contacts only)
Contact rating: 250 V AC, 8 A (resistive load)
250 V AC, 2 A (cos φ = 0.4)
24 V DC, 2.5 A (L/R = 0.7 ms)
Life: At least 120000 cycles (at the rated resistive load)
At least 100000 cycles (at the rated inductive load)
Minimum requirements for switching:
24 V DC, 40 mA
Voltage pulse output (For SSR drive)
Voltage between
terminals at open:
19 V DC±15 %
Internal resistance: 82 Ω±0.5 %
Allowable current:
Max. 24 mA DC (a higher current might cause output circuit failure)
OFF leak current: Max. 100 μA
Min. OFF time/
ON time:
1 ms when the time proportional cycle time is less than 10 s.
250 ms when the time proportional cycle time is more than 10 s.
Current output
Output type:
0 to 20 mA DC or 4 to 20 mA DC
Allowance load
resistance:
Max. 600 Ω
Output accuracy: ±0.1 %FS (at an ambient temperature of 23±2 °C)
However, ±1.0 %FS in a range of 0 to 1 mA.
Output resolution: 1/10000
Continuous voltage output
Output type: 0 to 5 V DC, 1 to 5 V DC or 0 to 10 V DC
Allowable load
resistance:
Min. 1000 Ω
Output accuracy: ±0.1 %FS (at an ambient temperature of 23±2 °C)
However, ±1 %FS at 0 to 0.05 V.
Output resolution: 1/10000
Auxiliary output
Current output
Output type:
0 to 20 mA DC or 4 to 20 mA DC
Allowable load
resistance:
Max. 600 Ω
Output accuracy: ±0.1 %FS (at an ambient temperature of 23±2 °C)
However, ±1 %FS at 0 to 1 mA.
Output resolution: 1/10000