4-16
Chapter 4 Maintenance and Troubleshooting of this Device
îîTable 4-5.
HART5
Indicator
Display
Diagnostics
Display Message
Description Countermeasures
Critical Status
Err.01
A-D CNV
Analog/Digital
Conversion Fault
An error occurred during
analog-to-digital conversion.
There is a problem with the
sensor.
Contact customer service.
Err.02
PROM
Sensor
Characteristic Data
Fault
An error was detected in the
sensor characteristic data.
Err.03
INPUT
Suspect Input Input data error
Err.04
CPU
CPU Fault CPU operation failure
There is a problem with the
printed circuit board.
Contact customer service.
Err.05
NVM
NVM Fault Nonvolatile memory error
Err.06
RAM
RAM Fault RAM failure
Err.07
ROM
ROM Fault ROM failure
Err.08
OUTPUT
Output Circuit
Fault
Output circuit failure
Internal Data
Inconsistency
Err.09
CONFIG
Invalid Database
Configuration data and/or
calibration data is invalid.