A-9
Appendix A  Maintenance and Troubleshooting of this Device
A2-4-6  Parameter adjustment
If diagnosis is judged to be not possible, the data collected under normal operating conditions 
(section A2-4-2) and when there is simulated clogging (section A2-4-3) can be analyzed and the 
parameters adjusted.
The reason why diagnosis cannot be performed is that the index value—even under normal 
operating conditions—is similar to or smaller than that when there is clogging, so the normal and 
clogged states cannot be distinguished. There are two primary causes leading for this situation.
•  A large amount of variation of the index under normal conditions
•  A small variation of the index when there is clogging
This situation may be improved by adjusting the parameters of the pressure frequency index 
diagnosis. The following describes the two cases.
(A) Variation of the index under normal operating conditions is large.
In this case, although the value of the index is small with simulated clogging, variation in the index 
is large under normal conditions, so the index value can be close to or equivalent to its value with 
clogging even when there is no clogging, as shown in the figure below.
Index value Index value
Maximum value 
under normal 
operating conditions
Minimum value 
under normal 
operating conditions
Maximum value 
under simulated
clogging
Minimum value 
under simulated 
clogging
Maximum value 
under normal 
operating conditions
Minimum value 
under normal 
operating conditions
Maximum value 
under simulated
clogging
Minimum value 
under simulated 
clogging
Normal condition Simulated clogging 
Normal condition Simulated clogging 
condition
Slight dierence Value being overlapping
In this case, it is necessary to examine the cause of the large variation that occurs under normal 
conditions, and to reduce this effect. Use the following the guidelines for adjustment.
Guidelines for parameter adjustment
The index value sometimes 
decreases significantly under normal 
operating conditions. At this time, 
the process variable changes or the 
standard deviation becomes large.
Increase the Press Freq Filter Constant in steps of 0.02–
0.05.
The index value under normal 
operating conditions changes 
significantly depending on the 
operating conditions.
Check whether the operating conditions are related to the 
process variable. If there is a PV range where the difference 
between the maximum index value and the minimum is 
relatively small, or a PV range where the minimum under 
normal conditions is not small, set Press Freq Calc PV 
High Limit and Press Freq Calc PV Low Limit to the values 
of this range. When these parameters are used, diagnosis 
should be carried out only when pressure is applied, and 
should be stopped when no pressure is applied.