A-13
Appendix A  Maintenance and Troubleshooting of this Device
Note that whether or not the cause is clogging can be inferred by comparing the pressure frequency 
index and the standard deviation with their values when conditions are normal. If the standard 
deviation increases at the same time that the pressure frequency index decreases, it is probable that, 
rather than a decrease in high-frequency fluctuation due to clogging, there has been an increase in 
low-frequency fluctuation due to some other cause.
Whether or not the status in which only one side of the connecting pipe is clogged is detected 
may vary depending on the various conditions such as fluid conditions or characteristics of the 
differential pressure generation mechanism (orifice, etc.). To understand whether or not detection 
is possible beforehand, it is strongly recommended that it is checked beforehand according to the 
clogging simulation test stated in section A3-4-3.
Depending on materials that cause clogging, even when clogging occurs, variations in index are 
small and no alarm is activated. For example, it is understood that when there are clearances, 
even when a clogged state due to gravel exists, the pressure fluctuation is transmitted through the 
clearances, and changes in index become small.
If the frequency of pressure fluctuation is abnormal from the beginning, as is a case where the 
connecting pipe was clogged from the start, it may not be possible to diagnose the clogging. Do the 
setup procedures (section A3-4) when the connecting pipe is operating normally.
Even if clogging occurs suddenly, the pressure frequency index will not change immediately. This 
is because it takes a few minutes to calculate the frequency of the pressure fluctuation with a high 
level of accuracy.
If the transmitter is installed in an environment subject to heavy vibration, the pressure frequency 
index may be affected, preventing correct diagnosis.