Chapter 3 Starting and Stopping this Device
(2) Starting Operation
(i) Applying process pressure
In the following procedure, valves are operated to apply the pressure of the process to this device,
and then the measured values are checked using the communicator.
Procedure
(1) Gradually open the manual master valve.
(ii) Checking measured values
• Using the communicator, check the measured values.
• After checking , disconnect the communication cable, attach the device's case cover, and switch
the process to normal operation.
• If the analog signal output, the displayed values, etc., do not match the process conditions, recheck
the setting range and the like. If this does not solve the problem, carry out the troubleshooting in
Chapter 4, or contact us.
• If the measurement output and display do not stabilize, refer to Chapter 4 and adjust the
damping time constant.
(iii) Cautions following confirmation of readings
After checking the measured values, confirm that the device's case cover is securely closed. If it is
not securely closed, rainwater and the like can enter the device and cause damage to the terminals,
electronics modules, etc., located inside.