Azbil Corporation Operation using the data setting device
Model MTG11A/18A, MTG11B/18B, MTG14C 5-31
Selecting the Electrode Status Output Mode
Setting the output mode when the Electrode Status Diagnostic function detects the
empty or scale on electrode status.
There are the following three electrode status output modes.
•OFF
ZERO
•HOLD
Default setting: OFF
Details of the “Electrode Status Output mode”
Output/Display
Parameter selection in the “Electrode status output mode”
OFF ZERO HOLD
Analog 4 – 20mA
output
Output values as the
meter measures.
Analog output is
fixed to 0% (4mA).
Analog output is
held at its last good
value.
Pulse output Output values as the
meter measures.
Pulse output is fixed
to 0 (does not
generate pulses).
Pulse output is held
at its present state.
Display Display the value as
it measures.
Flashes the message
0% and “Empty or
scale on electrode”
alternately (when %
flow rate is
specified for the
main display).
Flashes the message
0.000 RATE and
“Empty or scale on
electrode”
alternately (when
actual flow rate is
specified for the
main display).
Flashes the message
XXXXXXXX
(totalized value at
setup) and “Empty
or scale on
electrode”
alternately (when
totalized value is
specified for the
main display).
Flashes the values at
its last good values
and a message of
“Empty or scale on
electrode”
alternately.