Operation using the data setting device Azbil Corporation
6-70 Model MTG11A/18A, MTG11B/18B, MTG14C
Resetting the internal data to factory setting (default) [SHIP
DATA RECOV] function
By executing shipping data recovery, you can reset the two wired magnetic flowmeter
to the default factory setting. (Please note that all the data will be reset when executing
the [SHIP DATA RECOV] function.) Use the following procedure to execute the
shipping data recovery.
Step
Key Procedure SFC screen
1 Confirm that the SFC is set to
“READY”.
If it is not, press the key to
set it to “READY”.
2
or
Press the key to access the
CONFIG functions. Press the
key or key to display the
screen as shown on the right
3
or
Press the key. Press the
key or key to display the
screen as shown on the right
4 For [SHIPPING DATA
RECOVERY], press the key.
Shipping data recovery function
starts.
5 When shipping data recovery
completes, the display as shown on
the right appears.
6
Press the key and the screen
returns to the screen as in step 1.