Setting detector constant: [EX(mA)] function
Introduction
The detector constant of the converter is set at the factory according to the ordered
specifications. This constant can be changed.
Used when
When a combination between the detector and converter has been changed, the
detector constant set by the converter needs to be changed.
Procedure
Use the following procedure to set detector constant.
Step
Key Procedure SFC screen
1 Make sure that the SFC is set to
“READY”.
If it is not, press the key to set it
to “READY”.
2
Press the key to access the
CONFIG functions.
3
or
Press the key or key to
display the screen as shown on the
right.
4
Press the key.
Result:
The currently set detector constant
appears as shown on the right.
5 Press numeric keys to set the detector
constant. Setting range is 200 to
699.9.