Operation using the data setting device Azbil Corporation
6-62 Model MTG11A/18A, MTG11B/18B, MTG14C
Setting contact output status [DIGITAL I/O] function
When contact output (HI-LO ALARM) is selected in the previous page, use the
following procedure to set the contact output status (OPEN/CLOSE) in NORMAL
status.
Step
Key Procedure SFC screen
1 Confirm that the SFC is set to
“READY”.
If it is not, press the key to
set it to “READY”.
2
or
Press the key to access the
CONFIG functions. Press the
key or key to display the
screen as shown on the right
3
or
Press the key to access the
DIGITAL I/O function, press the
key or key to display
the screen as shown on the right.
The screen displays the setting of
the contact output status (OPEN/
CLOSE) in the actual NORMAL
status.
or
4
Press the key and select the
status to be set.
You can select OPEN or CLOSE.
5
Press the key.
The changed setting is saved to the
SFC.
6
or
Press the key or key to
show this screen.