Setting or changing low flow cutoff: [CUT-OFF] function
Introduction
When a fluid in the detector is flowing extremely slowly, the converter judges that the
fluid is stationary and outputs a signal (4 mA DC in case of analog output) equivalent
to a flow rate of zero. The value, which becomes the threshold of this judgment is
called “low flow cutoff”.
The low flow cutoff is set using a percentage over the upper range value of the flow
rate measurement range set by the URV.
Procedure
Use the following procedure to set low flow cutoff.
m CAUTION
The low flow cutoff is a factor of extreme importance that affects the operation of the entire
control process. Define the range to be controlled and start the setting carefully.
Step
Key Procedure SFC screen
1 Confirm that the SFC is set to
“READY”.
If it is not, press the key to set
it to “READY”.
2
Press the key to access the
CONFIG functions.
3
Press the key.
4
Press the key.
5
Pressing the key changes a
numeric value to the right of CUT
OFF=ON displayed on the screen
from 0% up to 10% in 1 point
increments. Continuing to press the
key further sets CUT
OFF=OFF and displays CUT
OFF=ON 0% again. Display the low
flow cutoff to be set in the range of
1- to 10% on the screen.