Operation using the data setting device Azbil Corporation
6-60 Model MTG11A/18A, MTG11B/18B, MTG14C
Select pulse output / contact output [DIGITAL I/O] function
Two wired magnetic flowmeter can be configured for pulse output or contact output
other than the analog current output (4-20 mA).
Use the following procedure to configure the pulse output and contact output.
Step
Key Procedure SFC screen
1 Confirm that the SFC is set to
“READY”.
If it is not, press the key to
set it to “READY”.
2
or
Press the key to access the
CONFIG functions. Press the
key or key to display the
screen as shown on the right
3
or
Press the key to access the
DIGITAL I/O function, press the
key or key to display
the screen as shown on the right.
Present setting function appears.
DO NOT USED..... Pulse output
HI-LO ALARM..... Contact output
* Following function will appear
on the screen but are not available
for two wired magnetic flowmeter.
ALARM
DIAG
EMPTY
H1-L1/H2-L2 ALM
or
4
Press the key and specify the
function to be set.
5
Press the key.
The changed setting is saved to the
SFC.