Operation using the data setting device Azbil Corporation
6-80 Model MTG11A/18A, MTG11B/18B, MTG14C
Setting counter reset function [RESET TOTALZE] function
Resetting the totalized value and setting reset value are possible using the SFC. When
resetting the totalized value, two wired magnetic flowmeter internal counter will be
reset and start resetting from the reset value which has been set. You can enter the reset
value maximum of 10 figures to SFC, however for two wired magnetic flowmeter only
8 figures are effective. Use the following procedure to reset the totalized value and to
set the reset value.
Step
Key Procedure SFC screen
1 Confirm that the SFC is set to
“READY”.
If it is not, press the key to
set it to “READY”.
2
or
Press the key to access the
CONFIG functions. Press the
key or key to display the
screen as shown on the right.
3
or
Press the key to access the
TOTALIZER functions. Press the
key or key to display
the screen as shown on the right.
4
Press the key. Display the
actual reset value.
5 Enter the reset value to be set
pressing the numeric keys.
CLR
( No )
CLR
( No )
SFCM00006009D
B
CONF
H
NEXT
L
PREV
B
CONF
H
NEXT
L
PREV
SFCM00006020D
SFCM00006136D
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
SFCM00006155D
ENTER
( Yes )
NON-VOL
ENTER
( Yes )
NON-VOL
SFCM00006156D
SFCM00006157D