Operation using the data setting device Azbil Corporation
5-66 Model MTG11A/18A, MTG11B/18B, MTG14C
5-7-4 : Performing loop checks of pulse outputs
Pulse output check
The electromagnetic flowmeter can be used as a pulse generator to check pulse
outputs.
This screen appears when pulse output has been selected in FUNC SET of
ENGINEERING MODE (see “5-6-2 : Selecting Pulse Output, Electrode Status Output
or High Low Status Output”).
Default setting
Displays the current output value.
Setting range
Range settings are allowed ranging from 0 to 100%.
Perform loop checks of pulse outputs in accordance with the following procedure:
Step Procedure Screen
1 Enter MAINTENANCE MODE in accordance
with the entry into MAINTENANCE MODE (see
section 5-5-9 on page 5-36). Then display the
screen at right.
2 Press the key to move the cursor to the OFF
position.
Press the - key. With the display switched from
OFF to ON, the output check mode is then active.
3 Press the key to display the screen at right.
4 Press the key to move the cursor to the position
under a desired value to be checked.
5 Pressing the or key, change the value to the
desired value to be checked. On the screen at
right, a frequency pulse corresponding to flow
rate signal 100% is output.
6 Press the key to move the cursor to the position
shown on the screen at right.
Movement to another screen by using the or
key returns to a pulse output according to the
actual flow rate.
20.0 %
> OUTPUT CHECK
MODE OFF
20.0 %
> OUTPUT CHECK
MODE OFF
20.0 %
> OUTPUT CHECK
MODE ON
20.0 %
> OUTPUT CHECK
I.OUT 000.0%
20.0 %
> OUTPUT CHECK
P.OUT 000.0%
20.0 %
> OUTPUT CHECK
P.OUT 000.0%
20.0 %
> OUTPUT CHECK
I.OUT 100.0%
20.0 %
> OUTPUT CHECK
I.OUT 100.0%