Azbil Corporation Operation using the data setting device
Model MTG11A/18A, MTG11B/18B, MTG14C 6-33
8 ILLEGAL RESPONSE • Abnormal communication with the
electromagnetic flowmeter.
• Check the communication cable and load
resistance.
9 IN LOCAL MODE • The converter is currently being operated from
the display panel.
• At this time, it is not possible to communicate
from the SFC.
10 IN OUTPUT MODE • The converter is in constant current generation
mode.
• Press the key and then press the
key to cancel the mode.
11
INVALID DATABASE
• A critical failure. Stop the electromagnetic
flow meter.
• This error occurs because the converter
database has not been set correctly when the
power to the converter is turned ON.
• Re-enter the CONF data.
12 INVALID REQUEST • The requested function cannot be performed.
• Check the operation procedure of the SFC and
press the key.
13 LOCAL MODE • The converter is being operated.
• At this time, it is not possible to communicate
from the SFC.
14
NO XMTR.RESPONSE
• There is no response from the electromagnetic
flow meter.
• Check the communication cable and
measurement loop.
15 NVM FAULT • A critical failure. Stop the electromagnetic
flow meter.
• The non-volatile memory of the converter is
abnormal. Turn OFF the power and then turn it
ON again and check the operation.
• If the same message still appears after taking
the action above, contact an Azbil Corp.
representative.
16 PRINTER FAIL! • The printer does not operate.
No.
Error message Checkpoint and action