Instrument installation Azbil Corporation
2-12 Model MTG11A/18A, MTG11B/18B, MTG14C
Table 2-1 Fastening torque
Diameter and flange ratings Fastening torque N•m (kgf•cm)*
25 mm
(1 inch)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
21 to 31
21 to 32
11 to 17
22 to 34
(214 to 316)*
(214 to 326)*
(112 to 173)*
(224 to 347)*
40 mm
(1½ inch)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
22 to 32
22 to 34
13 to 18
36 to 57
(224 to 326)*
(224 to 347)*
(132 to 184)*
(367 to 581)*
50 mm
(2 inches)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
24 to 34
19 to 31
23 to 32
20 to 32
(245 to 347)*
(194 to 316)*
(235 to 326)*
(204 to 326)*
65 mm
(2½ inches)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
20 to 31
37 to 61
26 to 35
37 to 57
(204 to 316)*
(377 to 622)*
(265 to 357)*
(377 to 581)*
80 mm
(3 inches)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
20 to 31
37 to 61
26 to 35
37 to 57
(204 to 316)*
(377 to 622)*
(265 to 357)*
(377 to 581)*
100 mm
(4 inches)
JIS 10K
JIS 20K
ANSI/JPI 150
ANSI/JPI 300
22 to 33
41 to 66
21 to 31
43 to 66
(224 to 337)*
(418 to 673)*
(214 to 316)*
(439 to 673)*