3 Phase 51 Pickup. This setting selects the overcurrent pickup threshold for three-phase generator
connections. A 51 Pickup setting of 0.18 to 1.18 Aac (style X1X1) or 0.9 to 7.75 Aac (style X5X1) may be
entered.
3 Phase 51 Time Dial. When three-phase generator connections are used, this setting selects the time
delay from when an overcurrent condition is detected and an overcurrent annunciation (trip) occurs. The
51 Time Dial setting operates in conjunction with the 51 Curve setting. When the F, Fixed Time curve
setting is selected, the 51 Time Dial setting is adjustable from 0 to 30 seconds and determines the
overcurrent time delay with no regard to the generator current level. When one of the 16 inverse curve
settings are selected, the 51 Time Dial setting (adjustable from a multiplier of 0 to 9.9) along with the level
of measured generator current determines the overcurrent time delay.
3 Phase 51 Curve. When three-phase generator connections are used, the 51 Curve setting operates in
conjunction with the 51 Time Dial setting. Selecting a 51 Curve setting of F, Fixed Time causes the 51
Time Dial setting to determine the overcurrent time delay with no regard to the generator current level.
When one of the 16 inverse curve settings are selected, the 51 Time Dial setting, along with the level of
the measured generator current, determines the overcurrent time delay. The overcurrent curve setting
selections are listed below.
A, Standard Inverse
B, Very Inverse
C, Extremely Inverse
D, Definite
E1, Extremely Inverse
E2, Extremely Inverse
F, Fixed Time
G, Long Inverse
I1, Inverse
I2, Inverse
L1, Long Inverse
L2, Long Inverse
M, Moderately Inverse
S1, Short Inverse
S2, Short Inverse
V1, Very Inverse
V2, Very Inverse
3 Phase 51 Alarm Configuration. This setting selects how a three-phase overcurrent condition is
annunciated. An overcurrent condition can be configured to trigger a pre-alarm, alarm, or no annunciation.
Single Phase 51 Pickup. This setting selects the overcurrent pickup threshold for single-phase
generator connections. A 51 Pickup setting of 0.18 to 1.18 Aac (style X1X1) or 0.9 to 7.75 Aac (style
X5X1) may be entered.
Single Phase 51 Time Dial. When single-phase generator connections are used, this setting selects the
time delay from when an overcurrent condition is detected and an overcurrent annunciation (trip) occurs.
The 51 Time Dial setting operates in conjunction with the 51 Curve setting. When the F, Fixed Time curve
setting is selected, the 51 Time Dial setting is adjustable from 0 to 30 seconds and determines the
overcurrent time delay with no regard to the generator current level. When one of the 16 inverse curve
settings are selected, the 51 Time Dial setting (adjustable from a multiplier of 0 to 9.9) along with the level
of measured generator current determines the overcurrent time delay.
Single Phase 51 Curve. When single-phase generator connections are used, the 51 Curve setting
operates in conjunction with the 51 Time Dial setting. Selecting a 51 Curve setting of F, Fixed Time
causes the 51 Time Dial setting to determine the overcurrent time delay with no regard to the generator
current level. When one of the 16 inverse curve settings are selected, the 51 Time Dial setting, along with
the level of the measured generator current, determines the overcurrent time delay. The overcurrent
curve setting selections are listed below.
A, Standard Inverse
B, Very Inverse
C, Extremely Inverse
D, Definite
E1, Extremely Inverse
E2, Extremely Inverse
F, Fixed Time
G, Long Inverse
I1, Inverse
I2, Inverse
L1, Long Inverse
L2, Long Inverse
M, Moderately Inverse
S1, Short Inverse
S2, Short Inverse
V1, Very Inverse
V2, Very Inverse
Single Phase 51 Alarm Configuration. This setting selects how a single-phase overcurrent condition is
annunciated. An overcurrent condition can be configured to trigger a pre-alarm, alarm, or no annunciation.
9355400990 Rev H DGC-500 BESTCOMS Software 4-15