6 | Electrical installation Baumer
34 Operating Manual IDC200 | V1.0
6 Electrical installation
6.1 General instructions for electric installation
NOTICE
Device damage due to faulty power supply.
The device can be damaged due to faulty power supply.
a) Operate the device only with protected low voltage and safe electrical isolation of protection
class III.
NOTICE
Device damage or unintended operation due to work on live parts.
Any wiring work on live parts may lead to unintentional operation.
a) Prior to performing any wiring work disconnect power supply.
b) Only connect or disconnect any terminals when not live.
NOTICE
IP50 protection will still be present even if the protective plug is removed.
Remove the protective plug for the shortest time possible and only in a clean ambiance (free
from dust, liquids, etc.).
n
The sensor's USB interface is for data transfer only, not for power supply. Power supply al-
ways via the 12-pin M12 connector.
n
Prerequisites for IP rating:
▪ Cable connection present at the process interface (12-pin M12 connector).
▪ The USB interface must be closed during operation (protective plug) to achieve IP67. Uti-
lizing the HID protocol with hence missing protective plug will achieve IP50 rating.
6.2 Connecting the sensor to the electrical system
NOTICE
Use a power unit for sensor supply. The USB interface is intended for data transfer only. Power
supply is always via the 12-pin M12 connector.
Instruction:
a) Ensure that the system is disconnected from power.
b) Connect the sensor according to the pin assignment.