106 CT-600-2
Address Signal
No.
Signal name Unit
%MW40208 - %MW40209 88 Compressor 2 status economizer valve
%MW40210 - %MW40211 89 Compressor 2 status high pressure switch
%MW40212 - %MW40213 90 Compressor 2 status oil flow/level switch
%MW40214 - %MW40215 91 Compressor 2 status oil pressure switch
(OS85) / oil pressure (OS95)
-/bara
%MW40216 - %MW40217 92 Compressor 2 general alarm status
%MW40218 - %MW40219 93 Compressor 2 ready for operation status
%MW40220 - %MW40221 94 Compressor 2 capacity setpoint %
%MW40222 - %MW40223 95 Compressor 2 actual capacity %
%MW40224 - %MW40225 96 Compressor 2 running hours h
%MW40226 - %MW40227 97 Reserved (not used yet)
%MW40228 - %MW40229 98 Compressor 2 highest ranked alarm index
8
...
... ... ...
%MW40232 - %MW40233 100 Compressor 3 suction pressure bara
%MW40234 - %MW40235 101 Compressor 3 discharge pressure bara
%MW40236 - %MW40237 102 Compressor 3 discharge temperature °C
%MW40238 - %MW40239 103 Compressor 3 discharge superheat °C
%MW40240 - %MW40241 104 Compressor 3 drive shaft frequency Hz
%MW40242 - %MW40243 105 Compressor 3 motor current A
%MW40244 - %MW40245 106 Compressor 3 actual CR position %
%MW40246 - %MW40247 107 Compressor 3 status oil valve
%MW40248 - %MW40249 108 Compressor 3 status economizer valve
%MW40250 - %MW40251 109 Compressor 3 status high pressure switch
%MW40252 - %MW40253 110 Compressor 3 status oil flow/level switch
%MW40254 - %MW40255 111 Compressor 3 status oil pressure switch
(OS85) / oil pressure (OS95)
-/bara
%MW40256 - %MW40257 112 Compressor 3 general alarm status
%MW40258 - %MW40259 113 Compressor 3 ready for operation status
%MW40260 - %MW40261 114 Compressor 3 capacity setpoint %
%MW40262 - %MW40263 115 Compressor 3 actual capacity %
%MW40264 - %MW40265 116 Compressor 3 running hours h
%MW40266 - %MW40267 117 Reserved (not used yet)
%MW40268 - %MW40269 118 Compressor 3 highest ranked alarm index
5
...
... ... ...
5
See section 14.2 for reference to compressor specific alarm index numbers.