Description Symbol Unit
HCS03.1E-
W0070-_-05
HCS03.1E-
W0100-_-05
HCS03.1E-
W0150-_-05
HCS03.1E-
W0210-_-05
maximum output current at
I
out_base_4
; f
s
= 8 kHz; t = 60 s;
T = 5 min; K = 1,5
13)
I
out_peak4_8
A 34,02 51,94 75,38 112,29
base load current at I
out_peak_4
;
f
s
= 8 kHz; t = 60 s; T = 5 min; K = 1,5
I
out_base4_8
A 22,68 34,62 50,26 74,86
maximum output current at
I
out_base_4
; f
s
= 12 kHz; t = 60 s;
T = 5 min; K = 1,5
14)
I
out_peak4_12
A 24,90 37,66 55,12 80,57
base load current at I
out_peak_4
;
f
s
= 12 kHz; t = 60 s; T = 5 min;
K = 1,5
I
out_base4_12
A 16,60 25,10 36,75 53,71
maximum output current at
I
out_base_4
; f
s
= 16 kHz; t = 60 s;
T = 5 min; K = 1,5
15)
I
out_peak4_16
A 18,73 28,08 41,70 60,61
base load current at I
out_peak_4
;
f
s
= 16 kHz; t = 60 s; T = 5 min;
K = 1,5
I
out_base4_16
A 12,49 18,72 27,80 40,41
maximum output current at
I
out_base_5
; f
s
= 2 kHz; t = 60 s;
T = 10 min; K = 1,1
16)
I
out_peak5_2
A -
base load current at I
out_peak_5
;
f
s
= 2 kHz; t = 60 s; T = 10 min;
K = 1,1
I
out_base5_2
A -
maximum output current at
I
out_base_5
; f
s
= 4 kHz; t = 60 s;
T = 10 min; K = 1,1
17)
I
out_peak5_4
A 46,36 73,69 98,64 150,11
base load current at I
out_peak_5
;
f
s
= 4 kHz; t = 60 s; T = 10 min;
K = 1,1
I
out_base5_4
A 42,14 66,99 89,67 136,47
maximum output current at
I
out_base_5
; f
s
= 8 kHz; t = 60 s;
T = 10 min; K = 1,1
18)
I
out_peak5_8
A 33,06 50,97 68,66 103,39
base load current at I
out_peak_5
;
f
s
= 8 kHz; t = 60 s; T = 10 min;
K = 1,1
I
out_base5_8
A 30,05 46,34 62,42 93,99
maximum output current at
I
out_base_5
; f
s
= 12 kHz; t = 60 s;
T = 10 min; K = 1,1
19)
I
out_peak5_12
A 24,20 36,95 50,13 74,09
base load current at I
out_peak_5
;
f
s
= 12 kHz; t = 60 s; T = 10 min;
K = 1,1
I
out_base5_12
A 22,00 33,59 45,57 67,36
Project Planning Manual | Rexroth IndraDrive Electric Drives
and Controls
| Bosch Rexroth AG 89/369
Power Sections for Converters - IndraDrive C