Maintenance and troubleshooting
10.3. If you encounter problems
Message
displayed
4...20 mA output,
if present
Meaning Recommended actio
ERR 2 22 mA The Parameters menu cannot be accessed.
Read fault of the menu: the process is not stopped.
Press the ENTER key to acknowledge the
message.
If the failure occurs regularly, contact your
retailer.
ERR 11 - The span and/or offset values entered during
adjustment of the 4...20 mA output are out of range:
offset < 3 mA or > 5 mA
and/or span <18.5 mA or > 21.5 mA
Press the ENTER key to go back to the Test
menu.
The device operates with the previous adjustment
values.