Technical data
6.8 Electrical data
WARNING!
OnlycircuitswithlimitedpowermaybeusedforULapprovedcomponentsaccordingto“NECClass2”.
6.8.1 Electrical data, without eldbus communication
Protection class III as per DIN EN 61140 (VDE 0140-1)
Connections Cable gland M16 x 1.5, wrench size 22 (clamping area 5 – 10 mm)
with screw-type terminals for cable cross-sections 0.14 – 1.5 mm²
Circular plug-in connector (M12 x 1, 8-pin)
Operating voltage 24 V DC ± 25%, max. residual ripple 10 %
Current consumption max. 190 mA
Power consumption max. 3.5 W
Input resistance
for set-point value signal 75 at 0/4 – 20 mA / 12 bit resolution
Analogue position feedback
max. load
for current output 0/4 – 20 mA 560
Digitalinput 0–5V=logical“0”,12-30V=logical“1”
logic invertible in software
Communications interface Connection to PC via USB bus interface set
Communication software Bürkert Communicator
english
Type 8694 REV.2