Control and display elements
7.4 Function of the DIP switches
TooperatetheDIPswitchesandbuttons,makesurethatthelocalcontrollockisdeactivated/
unlocked(factorysetting):withcommunicationsoftwareoreldbuscommunication.
ON DIP
1
2 3 4
ATTENTION!
Breakageofthepneumaticconnectionpiecesduetorotationalimpact.
When unscrewing and screwing in the body casing or transparent cap, do not hold the actuator of the
process valve but the basic housing.
To operate the DIP switches, unscrew the transparent cap
Body casing
Basic housing
Actuator
Transparent cap
Figure 15: Open positioner
DIP Switches Position Function
1 ON
Reversaloftheeectivedirectionoftheset-pointvalue(DIR.CMD)
(set-point value 20 – 4 mA corresponds to position 0 – 100 %), descending
OFF
Normaleectivedirectionoftheset-pointvalue
(set-point value 4 – 20 mA corresponds to position 0 – 100 %), ascending
2 ON Sealing function active. The valve completely closes below 2 %
15)
and
opens above 98 % of the set-point value (CUTOFF)
OFF No sealing function
3 ON Characteristic correction for adjustment of the operating characteristic
(linearization of the process characteristic CHARACT)
16)
OFF Linear characteristic
4 ON Operating status MANUAL (BY HAND)
OFF Operating status AUTOMATIC (AUTO)
Table 9: DIP Switches
15) Factory setting, can be changed via communications software.
16) The characteristic type can be changed via communications software.