Control and display elements
IO-Link error No valid process data is
received
- Check connection to the IO-Link master
- Check whether valid setpoints are sent to
the device via the IO-Link interface
X.TUNE error occurred The last X.TUNE was not
successful.
-Check compressed air supply
-Run X.TUNE again
Actuator supply is down The actuator supply voltage is
too low. Only with IO-Link
Check actuator supply voltage
POS.Monitor The set-point position is not
reached
-Run X.TUNE
-Check compressed air supply.
CMD sensor break
Cable break of the set-point
value signal.. The message can
be parameterized (see “16.2.7”)
Check the signal line of the set-point value
Table 16: Messages