49
Pneumatic installation
Move actuator to end position
Turn the hand levers to the right using a screwdriver.
Note: - do not press the hand levers when turning them
- observe the sequence as described below
→ 1. Actuate hand lever pilot valve deaeration.
→ 2. Actuate hand lever pilot valve aeration.
Both hand levers point to the right.
The actuator moves to the end position.
2.1.
1.2.
Type 8694 for highairowrate
Figure 33: Move actuator to end position
Move actuator back to the rest position
Turn the hand levers to the left using a screwdriver.
Note: - do not press the hand levers when turning them
- observe the sequence as described below
→ 1. Actuate hand lever pilot valve aeration.
→ 2. Actuate hand lever pilot valve deaeration.
Both hand levers point to the left (normal position).
The actuator moves by spring force to the rest position.
Type 8694 for highairowrate
1.2.
2.1.
Figure 34: Move actuator back to the rest position
Caution:
Ifthepilotvalvesareactuated,electricalcontrolisnotpossible.
▶ Move hand levers to normal position before starting up the device.
english
Type 8694 REV.2