67
VFDFaultF4 77 5033 ANALOG INPUT nvoVFDFaultF4 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF5 78 5034 ANALOG INPUT nvoVFDFaultF5 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF6 79 5035 ANALOG INPUT nvoVFDFaultF6 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF7 80 5036 ANALOG INPUT nvoVFDFaultF7 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF8 81 5037 ANALOG INPUT nvoVFDFaultF8 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF9 82 5038 ANALOG INPUT nvoVFDFaultF9 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDFaultF10 83 5039 ANALOG INPUT nvoVFDFaultF10 SNVT_count Monitor Reference VFD Manual Fault Codes
VFDVoltageF1 84 5040 ANALOG INPUT nvoVFDVoltsF1 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF2 85 5041 ANALOG INPUT nvoVFDVoltsF2 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF3 86 5042 ANALOG INPUT nvoVFDVoltsF3 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF4 87 5043 ANALOG INPUT nvoVFDVoltsF4 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF5 88 5044 ANALOG INPUT nvoVFDVoltsF5 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF6 89 5045 ANALOG INPUT nvoVFDVoltsF6 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF7 90 5046 ANALOG INPUT nvoVFDVoltsF7 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF8 91 5047 ANALOG INPUT nvoVFDVoltsF8 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF9 92 5048 ANALOG INPUT nvoVFDVoltsF9 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDVoltageF10 93 5049 ANALOG INPUT nvoVFDVoltsF10 SNVT_count Monitor Voltage from VFD to Fan Motor (VAC)
VFDLoadF1 94 5060 ANALOG INPUT nvoVFDLoadF1 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF2 95 5061 ANALOG INPUT nvoVFDLoadF2 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF3 96 5062 ANALOG INPUT nvoVFDLoadF3 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF4 97 5063 ANALOG INPUT nvoVFDLoadF4 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF5 98 5064 ANALOG INPUT nvoVFDLoadF5 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF6 99 5065 ANALOG INPUT nvoVFDLoadF6 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF7 100 5066 ANALOG INPUT nvoVFDLoadF7 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF8 101 5067 ANALOG INPUT nvoVFDLoadF8 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF9 102 5068 ANALOG INPUT nvoVFDLoadF9 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDLoadF10 103 5069 ANALOG INPUT nvoVFDLoadF10 SNVT_count Monitor Motor Load as a % of VFD Output Current (%)
VFDTempF1 104 5050 ANALOG INPUT nvoVFDTempF1 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF2 105 5051 ANALOG INPUT nvoVFDTempF2 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF3 106 5052 ANALOG INPUT nvoVFDTempF3 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF4 107 5053 ANALOG INPUT nvoVFDTempF4 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF5 108 5054 ANALOG INPUT nvoVFDTempF5 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF6 109 5055 ANALOG INPUT nvoVFDTempF6 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF7 110 5056 ANALOG INPUT nvoVFDTempF7 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF8 111 5057 ANALOG INPUT nvoVFDTempF8 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF9 112 5058 ANALOG INPUT nvoVFDTempF9 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
VFDTempF10 113 5059 ANALOG INPUT nvoVFDTempF10 SNVT_count_f Monitor VFD Heat sink Temperature (degrees C)
BMSOverrideActive 114 5300-0 BINARY INPUT nvoBMSOverride SNVT_count Monitor 0 = No Hard Wired BMS Override, 1 = Hard Wired BMS Override
BoardFuseBlown 115 5300-4 BINARY INPUT nvoPCBFuseAlert SNVT_count Monitor 0 = Fuse OK, 1 = Blown or Missing ECPM03 Fuse
EmergencyShutdown 116 5300-5 BINARY INPUT nvoERShutdown SNVT_count Monitor 0 = No Emergency Shutdown, 1 = Hard Wired Emergency Shutdown
SystemBypassActive 117 5300-7 BINARY INPUT nvoBypassActive SNVT_count Monitor 0 = No System Bypass, 1 = System Bypass Activated
ErrorTempSensor1 118 5400-0…1 ANALOG INPUT nvoERRTempS1 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor2 119 5400-2…3 ANALOG INPUT nvoERRTempS2 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor3 120 5400-4…5 ANALOG INPUT nvoERRTempS3 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor4 121 5400-6…7 ANALOG INPUT nvoERRTempS4 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor5 122 5400-8…9 ANALOG INPUT nvoERRTempS5 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor6 123 5400-10…11 ANALOG INPUT nvoERRTempS6 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor7 124 5400-12…13 ANALOG INPUT nvoERRTempS7 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor8 125 5400-14…15 ANALOG INPUT nvoERRTempS8 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor9 126 5401-0…1 ANALOG INPUT nvoERRTempS9 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor10 127 5401-2…3 ANALOG INPUT nvoERRTempS10 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor11 128 5401-4…5 ANALOG INPUT nvoERRTempS11 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor12 129 5401-6…7 ANALOG INPUT nvoERRTempS12 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor13 130 5401-8…9 ANALOG INPUT nvoERRTempS13 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor14 131 5401-10…11 ANALOG INPUT nvoERRTempS14 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor15 132 5401-12…13 ANALOG INPUT nvoERRTempS15 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor16 133 5401-14…15 ANALOG INPUT nvoERRTempS16 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor17 134 5404-0…1 ANALOG INPUT nvoERRTempS17 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor18 135 5404-2…3 ANALOG INPUT nvoERRTempS18 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor19 136 5404-4…5 ANALOG INPUT nvoERRTempS19 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor20 137 5404-6…7 ANALOG INPUT nvoERRTempS20 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor21 138 5404-8…9 ANALOG INPUT nvoERRTempS21 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor22 139 5404-10…11 ANALOG INPUT nvoERRTempS22 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor23 140 5404-12…13 ANALOG INPUT nvoERRTempS23 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor24 141 5404-14…15 ANALOG INPUT nvoERRTempS24 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor25 142 5405-0…1 ANALOG INPUT nvoERRTempS25 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor26 143 5405-2…3 ANALOG INPUT nvoERRTempS26 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor27 144 5405-4…5 ANALOG INPUT nvoERRTempS27 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor28 145 5405-6…7 ANALOG INPUT nvoERRTempS28 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor29 146 5405-8…9 ANALOG INPUT nvoERRTempS29 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor30 147 5405-10…11 ANALOG INPUT nvoERRTempS30 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor31 148 5405-12…13 ANALOG INPUT nvoERRTempS31 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorTempSensor32 149 5405-14…15 ANALOG INPUT nvoERRTempS32 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor1 150 5408-0…1 ANALOG INPUT nvoERRHMISens1 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor2 151 5408-2…3 ANALOG INPUT nvoERRHMISens2 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor3 152 5408-4…5 ANALOG INPUT nvoERRHMISens3 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor4 153 5408-6…7 ANALOG INPUT nvoERRHMISens4 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor5 154 5408-8…9 ANALOG INPUT nvoERRHMISens5 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor6 155 5408-10…11 ANALOG INPUT nvoERRHMISens6 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor7 156 5408-12…13 ANALOG INPUT nvoERRHMISens7 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor8 157 5408-14…15 ANALOG INPUT nvoERRHMISens8 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor9 158 5409-0…1 ANALOG INPUT nvoERRHMISens9 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
ErrorHMISensor10 159 5409-2…3 ANALOG INPUT nvoERRHMISens10 SNVT_count Monitor 0 = No Fault, 1 = Broken Sensor, 2 = Missing Sensor, 3 = Missing Board/HMI
BACnet OBJECT NAME BACNET
Object ID
Modbus
Register
BACNET
Data Type
LON SNVT Name LON SNVT
Type
Function Default Range Description