68
StateVFD1 160 5550-LB ANALOG INPUT nvoStateVFD1 SNVT_count Monitor 1 = Off by Temperature,
2 = Off by High Temperature Alarm,
3 = Off by Low Temperature Alarm,
4 = Off by Emergency Shutdown,
5 = Off by Manual Mode Timer Expire,
6 = On by Temperature,
7 = On by HMI Command (Button Press),
8 = On by System Bypass,
9 = On by BMS 1,
10 = On by BMS 2,
11 = Off by HMI Command (Button Press)
StateVFD2 161 5550-HB ANALOG INPUT nvoStateVFD2 SNVT_count Monitor
StateVFD3 162 5551-LB ANALOG INPUT nvoStateVFD3 SNVT_count Monitor
StateVFD4 163 5551-HB ANALOG INPUT nvoStateVFD4 SNVT_count Monitor
StateVFD5 164 5552-LB ANALOG INPUT nvoStateVFD5 SNVT_count Monitor
StateVFD6 165 5552-HB ANALOG INPUT nvoStateVFD6 SNVT_count Monitor
StateVFD7 166 5553-LB ANALOG INPUT nvoStateVFD7 SNVT_count Monitor
StateVFD8 167 5553-HB ANALOG INPUT nvoStateVFD8 SNVT_count Monitor
StateVFD9 168 5554-LB ANALOG INPUT nvoStateVFD9 SNVT_count Monitor
StateVFD10 169 5554-HB ANALOG INPUT nvoStateVFD10 SNVT_count Monitor
MBFaultHMI1 170 5350-0 BINARY INPUT nvoMBFaultHMI1 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI2 171 5350-1 BINARY INPUT nvoMBFaultHMI2 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI3 172 5350-2 BINARY INPUT nvoMBFaultHMI3 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI4 173 5350-3 BINARY INPUT nvoMBFaultHMI4 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI5 174 5350-4 BINARY INPUT nvoMBFaultHMI5 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI6 175 5350-5 BINARY INPUT nvoMBFaultHMI6 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI7 176 5350-6 BINARY INPUT nvoMBFaultHMI7 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI8 177 5350-7 BINARY INPUT nvoMBFaultHMI8 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI9 178 5350-8 BINARY INPUT nvoMBFaultHMI9 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultHMI10 179 5350-9 BINARY INPUT nvoMBFaultHMI10 SNVT_count Monitor 0 = No Fault, 1 = HMI Modbus Communication Fault
MBFaultVFD1 180 5352-0 BINARY INPUT nvoMBFaultVFD1 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD2 181 5352-1 BINARY INPUT nvoMBFaultVFD2 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD3 182 5352-2 BINARY INPUT nvoMBFaultVFD3 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD4 183 5352-3 BINARY INPUT nvoMBFaultVFD4 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD5 184 5352-4 BINARY INPUT nvoMBFaultVFD5 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD6 185 5352-5 BINARY INPUT nvoMBFaultVFD6 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD7 186 5352-6 BINARY INPUT nvoMBFaultVFD7 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD8 187 5352-7 BINARY INPUT nvoMBFaultVFD8 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD9 188 5352-8 BINARY INPUT nvoMBFaultVFD9 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultVFD10 189 5352-9 BINARY INPUT nvoMBFaultVFD10 SNVT_count Monitor 0 = No Fault, 1 = VFD Modbus Communication Fault
MBFaultEXP1 190 5354-0 BINARY INPUT nvoMBFaultEXP1 SNVT_count Monitor 0 = No Fault, 1 = Expansion Board Modbus Communication Fault
MBFaultEXP2 191 5354-1 BINARY INPUT nvoMBFaultEXP2 SNVT_count Monitor 0 = No Fault, 1 = Expansion Board Modbus Communication Fault
MBFaultEXP3 192 5354-2 BINARY INPUT nvoMBFaultEXP3 SNVT_count Monitor 0 = No Fault, 1 = Expansion Board Modbus Communication Fault
ButtonG1 193 13020
BINARY VARIABLE
nviButtonG1 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG2 194 13021
BINARY VARIABLE
nviButtonG2 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG3 195 13022
BINARY VARIABLE
nviButtonG3 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG4 196 13023
BINARY VARIABLE
nviButtonG4 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG5 197 13024
BINARY VARIABLE
nviButtonG5 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG6 198 13025
BINARY VARIABLE
nviButtonG6 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG7 199 13026
BINARY VARIABLE
nviButtonG7 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG8 200 13027
BINARY VARIABLE
nviButtonG8 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG9 201 13028
BINARY VARIABLE
nviButtonG9 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
ButtonG10 202 13029
BINARY VARIABLE
nviButtonG10 SNVT_count Control 0 0 or 1 Fan Group State, 1 = ON , 0 = OFF in DDC Manual Mode
SpeedG1 203 13030
ANALOG VARIABLE
nviSpeedG1 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG2 204 13031
ANALOG VARIABLE
nviSpeedG2 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG3 205 13032
ANALOG VARIABLE
nviSpeedG3 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG4 206 13033
ANALOG VARIABLE
nviSpeedG4 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG5 207 13034
ANALOG VARIABLE
nviSpeedG5 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG6 208 13035
ANALOG VARIABLE
nviSpeedG6 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG7 209 13036
ANALOG VARIABLE
nviSpeedG7 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG8 210 13037
ANALOG VARIABLE
nviSpeedG8 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG9 211 13038
ANALOG VARIABLE
nviSpeedG9 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
SpeedG10 212 13039
ANALOG VARIABLE
nviSpeedG10 SNVT_count Control 0% 0 to 100% Fan Group Speed, 0% = Min Fan Group Speed, 100% = Max Fan Group Speed
DirectionF1 213 13010
BINARY VARIABLE
nviDirF1 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF2 214 13011
BINARY VARIABLE
nviDirF2 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF3 215 13012
BINARY VARIABLE
nviDirF3 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF4 216 13013
BINARY VARIABLE
nviDirF4 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF5 217 13014
BINARY VARIABLE
nviDirF5 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF6 218 13015
BINARY VARIABLE
nviDirF6 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF7 219 13016
BINARY VARIABLE
nviDirF7 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF8 220 13017
BINARY VARIABLE
nviDirF8 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF9 221 13018
BINARY VARIABLE
nviDirF9 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
DirectionF10 222 13019
BINARY VARIABLE
nviDirF10 SNVT_count Control 0 0 or 1 Fan Direction, 0 = Forward, 1 = Reverse
ModeG1 223 13000
BINARY VARIABLE
nviModeG1 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG2 224 13001
BINARY VARIABLE
nviModeG2 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG3 225 13002
BINARY VARIABLE
nviModeG3 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG4 226 13003
BINARY VARIABLE
nviModeG4 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG5 227 13004
BINARY VARIABLE
nviModeG5 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG6 228 13005
BINARY VARIABLE
nviModeG6 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG7 229 13006
BINARY VARIABLE
nviModeG7 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG8 230 13007
BINARY VARIABLE
nviModeG8 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG9 231 13008
BINARY VARIABLE
nviModeG9 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
ModeG10 232 13009
BINARY VARIABLE
nviModeG10 SNVT_count Control 0 0 or 1 Fan Group Mode, 0 = DDC Auto, 1=DDC Manual
MaxG1 233 10246
ANALOG VARIABLE
nviMaxG1 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG2 234 10254
ANALOG VARIABLE
nviMaxG2 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG3 235 10262
ANALOG VARIABLE
nviMaxG3 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG4 236 10270
ANALOG VARIABLE
nviMaxG4 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG5 237 10278
ANALOG VARIABLE
nviMaxG5 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG6 238 10286
ANALOG VARIABLE
nviMaxG6 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG7 239 10294
ANALOG VARIABLE
nviMaxG7 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG8 240 10302
ANALOG VARIABLE
nviMaxG8 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG9 241 10310
ANALOG VARIABLE
nviMaxG9 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MaxG10 242 10318
ANALOG VARIABLE
nviMaxG10 SNVT_count Control 55 Hz/80 Hz Min to Max Maximum VFD Group Frequency (Hz), 1 decimal precision, i.e. 45.5 Hz = 455
MinG1 243 10247
ANALOG VARIABLE
nviMinG1 SNVT_count Control 15 Hz Min to Max Minimum VFD Group Frequency (Hz), 1 decimal precision, i.e. 33.5 Hz = 335
MinG2 244 10255
ANALOG VARIABLE
nviMinG2 SNVT_count Control 15 Hz Min to Max Minimum VFD Group Frequency (Hz), 1 decimal precision, i.e. 33.5 Hz = 335
MinG3 245 10263
ANALOG VARIABLE
nviMinG3 SNVT_count Control 15 Hz Min to Max Minimum VFD Group Frequency (Hz), 1 decimal precision, i.e. 33.5 Hz = 335
MinG4 246 10271
ANALOG VARIABLE
nviMinG4 SNVT_count Control 15 Hz Min to Max Minimum VFD Group Frequency (Hz), 1 decimal precision, i.e. 33.5 Hz = 335
BACnet OBJECT NAME BACNET
Object ID
Modbus
Register
BACNET
Data Type
LON SNVT Name LON SNVT
Type
Function Default Range Description