Addressing the Carrier® ChillerVu™
Carrier® ChillerVu™
(OPN-PSM-MPCXPE) Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation and Start-up Guide 9 All rights reserved
The Carrier® ChillerVu™ needs two addresses, one for the BACnet system and one for the IP network.
The Carrier®
ChillerVu™ needs...
That is
unique
on the...
Notes
See...
A BACnet Device
Instance
BACnet
system
You set the Carrier® ChillerVu™ address on the
controller's rotary switches.
NOTE
The Carrier® ChillerVu™ address is also
used to autogenerate the BACnet Device
Instance/Name for the router and the MS/TP
network number for the Open network.
See Configuring BACnet device instance and
network number.
To set the controller's
Device Instance
An IP address IP network You can use one of the following:
The
default
IP address that your system
creates:
IP address = 192.168.168.
x
where
x
is the controller network MAC address.
Subnet mask = 255.255.255.0
To use a default IP
address (page 10)
A DHCP IP address
To use a DHCP IP address
(page 11)
Assign a
custom
IP address
To use a custom IP
address (page 11)
NOTES
Carefully plan your addressing scheme to avoid duplicating addresses. If third-party devices are integrated
into the system, make sure your addresses do not conflict with their addresses.
The controller's BACnet network and IP address can be configured using the Local Access port. See To
communicate through the Local Access port with a USB Link (page 52).
To choose an IP addressing scheme
Carefully plan your addressing scheme to avoid duplicating addresses.
By default, the Carrier® ChillerVu™ is set up for assigned IP addressing. The default IP address settings are as
follows:
IP address = 192.168.168.x, where x = Carrier® ChillerVu™ address (rotary switch settings)
Subnet Mask = 255.255.255.0
Default Gateway = 192.168.168.254
Addressing the Carrier® ChillerVu™

Table of Contents

Related product manuals